DAAO6604-8
1500L Chilled Tank-Fed Emergency Shower & Eyewash Enclosure

  • Engineered for hot-climate industrial environments up to +55°C.
  • Suitable for:Indoor/Outdoor,Hot Climates(up to +55°C),Hazardous Areas
  • Certificate & Standard:ANSI Z 358.1-2014, EN15154.1/2:2006
  • Temperature Control:Water Chiller + Circulation System
  • Tepid Flushing Water:16–38°C design range
  • Enclosure Material:AISI 304 SS / AISI 316L SS Optional
  • Shower flow rate:≥75.7L/min, Eyewash flow rate:≥11.4L/min
  • Wall Thickness: 1.2mm; Pipe thickness: 2.5-3mm;
  • Working Pressure:2–6bar,Water Inlet:NPT1-1/4″,Drain Outlet:NPT2″
  • Water Level & Temperature Monitoring,Internal Lighting— Integrated
  • Audible & Visual Alarm, Remote Signal Interface,Automatic Water Filling,Anti-Scald Protection —Optional
  • Inlet size: NPT 1 1/4″ Drain size: NPT 2″
  • Hazardous-Area Configuration:ATEX / IECEx options according to project requirements
  • Dimensions:1200 × 1200 × 3950 mm,Approx. Weight:700 kg
  • Design Service Life:15 years
×

Download Product Catalog

Please enter your information to instantly view the PDF catalog.

download form

Description

The DAAO6604-8 is a temperature-controlled, tank-fed emergency shower and eyewash enclosure engineered for hot-climate industrial environments where stored or incoming water temperatures may exceed the suitable range for emergency flushing.

An integrated 1500 L insulated water tank, water chiller and circulation system work together to control flushing-water temperature under high ambient conditions. The standard configuration is designed for ambient temperatures from +5°C to +55°C, with project-engineered configurations available for more demanding operating conditions.
The self-contained tank provides a dedicated emergency water reserve where a reliable tepid-water supply is unavailable or cannot be guaranteed. The shower and eyewash system is designed to deliver the required emergency flushing flow, while the integrated circulation and temperature-control system continuously manages stored-water conditions.
A bottom collection tray and dedicated drain connection provide controlled discharge of used flushing water. Internal lighting improves visibility during emergency operation, while optional audible/visual alarms, DCS/PLC signal interfaces, automatic water filling, and hazardous-area electrical packages can be integrated according to project requirements.
Available in AISI 304 or AISI 316L stainless steel, the DAAO6604-8 can be engineered for chemical, petrochemical, oil & gas, energy, mining, and other high-temperature industrial applications.

Hazardous-Area Configuration
Project-specific hazardous-area packages are available with explosion-protected electrical components, including alarm devices, control/interface panels, conduit, instrumentation, and associated electrical equipment.
ATEX / IECEx configurations available according to project hazardous-area classification.

Alarm & Control Integration
Local audible/visual alarm and remote signal interfaces can be integrated with shower and eyewash activation. Hazardous-area configurations are available with explosion-protected alarm devices, control panels, and signal interface equipment for connection to site DCS/PLC systems.

Project-Engineered Configurations
The DAAO6604-8 can be configured beyond the standard specification for demanding EPC applications.
HOT CLIMATE CONTROL & ALARM
Extended ambient-temperature configurations Local alarm + DCS / PLC interface
HAZARDOUS AREA UTILITY CONFIGURATION
ATEX / IECEx electrical packages Tank capacity · Voltage · Cooling capacity · Auto-fill

  • 01 — Hot-Climate Operation up to +55°C
  • Engineered for high-ambient-temperature industrial installations where stored flushing water is exposed to significant environmental heat gain.
  • 02 — Active Water Cooling
  • Integrated chiller controls stored water temperature to maintain suitable emergency flushing conditions.
  • 03 — 1500L Self-Contained Water Reserve
  • Provides stored emergency flushing water where a continuous tepid-water supply is unavailable or unreliable.
  • 04 — Insulated Tank & Enclosure
  • PUF insulation reduces heat gain and improves temperature-control efficiency under high ambient conditions.
  • 05 — Integrated Drainage & Monitoring
  • Bottom collection tray, drain connection, water-level indication, and temperature monitoring support safe operation and routine inspection.
  • 06 — Alarm & Project Integration
  • Optional audible/visual alarm, DCS/PLC signal interface, hazardous-area electrical configuration, and automatic water filling.

Related Engineering Case Studies
See how chilled tank-fed emergency shower systems are applied in hot-climate industrial projects.
View Case Studies →

Enclosed Emergency Shower 1 1


Optional Accessories: Explosion-proof or non-explosion-proof chiller unit (suitable for hot climates);Immersion heater (suitable for cold climates);Explosion-proof or non-explosion-proof space heater; Brass/stainless steel pressure regulator; Side and rear panel insulation / water tank insulation; Water temperature sensor; Water level sensor; Spring-loaded door; Drainage channel and grating;